Cause
Why do photovoltaic power generation systems need to be equipped with fast shutdown devices?The use of rapid shutdown devices in photovoltaic (PV) systems has become increasingly important due YCRS Rapid Shutdown Device YCRS Rapid Shutdown Deviceto concerns about safety in recent years. PV system accidents often result in fires, and 80% of these fires are caused by DC voltage arcing. Additionally, because many distributed PV systems are installed in densely populated areas or near industrial facilities, any accidents or failures can lead to significant losses of life and property. Therefore, many countries require that PV systems be equipped with component-level rapid shutdown devices in order to eliminate DC voltage in emergency situations and protect the safety of firefighting and maintenance personnel, as well as to ensure the overall safety of the system. In the event of a fire or other emergency, maintenance personnel can quickly disconnect each component by closing the YCRS device and eliminating the DC voltage, thus protecting the safety of firefighting and maintenance personnel.
Selection
YCRS |
— |
50 |
2 |
MC4 |
Enterprise code |
Rated current |
Wiring mode |
Joint type |
Firefighter safety switch |
13: 13A
20: 20A
25: 25A
40: 40A
50: 50A |
2: 2P
4: 4P
4B: 4B
6: 6P
8: 8P
10: 10P
12: 12P
14: 14P
16: 16P
18: 18P
20: 20P |
MC4: MC4 joint /: No |
Note: RP Rapid Shutdown Switch/Panel
Technical data
Model |
YCRS-2/4P/4B |
YCRS-6/8 |
YCRS-10 |
YCRS-12~20 Large |
String voltage(VDC) |
300~1500 |
300~1500 |
300~1500 |
300~1500 |
String current A |
9~55 |
9~55 |
9~55 |
9~55 |
Return circuit |
1/2 |
3/4/5 |
3/4/5 |
6/8/10 |
Isolation switch circuit connection method |
2/4/4B |
6/8 |
10 |
12/16/20 |
Working voltage |
100Vac-270Vac |
100Vac-270Vac |
100Vac-270Vac |
100Vac-270Vac |
Rated voltage |
230Vac |
230Vac |
230Vac |
230Vac |
Rated current |
30mA |
30mA |
30mA |
60mA |
Starting (loading) current |
100mA(AVG) |
100mA(AVG) |
100mA(AVG) |
200mA(AVG) |
Action current |
300mA(Max) |
300mA(Max) |
300mA(Max) |
600mA(Max) |
Contact action conditions |
24Vdc-300mA(Max) |
24Vdc-300mA(Max) |
24Vdc-300mA(Max) |
24Vdc-300mA(Max) |
Working temperature |
-20℃-+50℃ |
-20℃-+50℃ |
-20℃-+50℃ |
-20℃-+50℃ |
Maximum temperature before automatic shutdown |
+70℃ |
+70℃ |
+70℃ |
+70℃ |
Storage temperature |
-40℃-+85℃ |
-40℃-+85℃ |
-40℃-+85℃ |
-40℃-+85℃ |
Protection degree |
IP66 |
IP66 |
IP66 |
IP66 |
Overcurrent protection |
II |
II |
II |
II |
Authentication |
CE |
CE |
CE |
CE |
Standard |
EN60947-1&3 |
EN60947-1&3 |
EN60947-1&3 |
EN60947-1&3 |
Mechanical life |
10000 |
10000 |
10000 |
10000 |
Load operands(PV1) |
>1500 |
>1500 |
>1500 |
>1500 |
Current/Voltage category parameter table(DC-PV1)
Data of ERS refer to built-in DC isolators.
Data according to IEC60947-3(ed.3.2):2015,UL508i.Utilization category DC-PV1. |
Pole number |
Circuit |
Model |
600V |
800V |
1000V |
1200V |
1500V |
32 |
26 |
13 |
10 |
5 |
2 |
1 |
YCRS-13 2 |
40 |
30 |
20 |
12 |
6 |
2 |
1 |
YCRS-20 2 |
55 |
40 |
25 |
15 |
8 |
2 |
1 |
YCRS-25 2 |
/ |
50 |
40 |
30 |
20 |
2 |
1 |
YCRS-40 2 |
/ |
55 |
50 |
40 |
30 |
2 |
1 |
YCRS-50 2 |
32 |
26 |
13 |
10 |
5 |
4 |
2 |
YCRS-13 4 |
40 |
30 |
20 |
12 |
6 |
4 |
2 |
YCRS-20 4 |
55 |
40 |
25 |
15 |
8 |
4 |
2 |
YCRS-25 4 |
/ |
50 |
40 |
30 |
20 |
4 |
2 |
YCRS-40 4 |
/ |
55 |
50 |
40 |
30 |
4 |
2 |
YCRS-50 4 |
32 |
26 |
13 |
10 |
5 |
4 |
1 |
YCRS-13 4B |
40 |
40 |
40 |
30 |
20 |
4 |
1 |
YCRS-20 4B |
/ |
/ |
55 |
40 |
30 |
4 |
1 |
YCRS-25 4B |
/ |
/ |
/ |
/ |
45 |
4 |
1 |
YCRS-40 4B |
/ |
/ |
/ |
/ |
50 |
4 |
1 |
YCRS-50 4B |
32 |
26 |
13 |
10 |
5 |
6 |
3 |
YCRS-13 6 |
40 |
30 |
20 |
12 |
6 |
6 |
3 |
YCRS-20 6 |
55 |
45 |
25 |
15 |
8 |
6 |
3 |
YCRS-25 6 |
/ |
50 |
40 |
30 |
20 |
6 |
3 |
YCRS-40 6 |
/ |
55 |
50 |
40 |
30 |
6 |
3 |
YCRS-50 6 |
32 |
26 |
13 |
10 |
5 |
8 |
4 |
YCRS-13 8 |
40 |
30 |
20 |
12 |
6 |
8 |
4 |
YCRS-20 8 |
55 |
40 |
25 |
15 |
8 |
8 |
4 |
YCRS-25 8 |
/ |
50 |
40 |
30 |
20 |
8 |
4 |
YCRS-40 8 |
/ |
55 |
50 |
40 |
30 |
8 |
4 |
YCRS-50 8 |
32 |
26 |
13 |
10 |
5 |
10 |
5 |
YCRS-13 10 |
40 |
30 |
20 |
12 |
6 |
10 |
5 |
YCRS-20 10 |
55 |
40 |
25 |
15 |
8 |
10 |
5 |
YCRS-25 10 |
/ |
50 |
40 |
30 |
20 |
10 |
5 |
YCRS-40 10 |
/ |
55 |
50 |
40 |
30 |
10 |
5 |
YCRS-50 10 |
32 |
26 |
13 |
10 |
5 |
12 |
6 |
YCRS-13 12 |
40 |
30 |
20 |
12 |
6 |
12 |
6 |
YCRS-20 12 |
55 |
40 |
25 |
15 |
8 |
12 |
6 |
YCRS-25 12 |
/ |
50 |
40 |
30 |
20 |
12 |
6 |
YCRS-40 12 |
/ |
55 |
50 |
40 |
30 |
12 |
6 |
YCRS-50 12 |
32 |
26 |
13 |
10 |
5 |
14 |
6 |
YCRS-13 14 |
40 |
30 |
20 |
12 |
6 |
14 |
6 |
YCRS-20 14 |
55 |
40 |
25 |
15 |
8 |
14 |
6 |
YCRS-25 14 |
/ |
50 |
40 |
30 |
20 |
14 |
6 |
YCRS-40 14 |
/ |
55 |
50 |
40 |
30 |
14 |
6 |
YCRS-50 14 |
Note: RP Rapid Shutdown Switch/Panel
Current/Voltage category parameter table(DC-PV1)
Data of ERS refer to built-in DC isolators.
Data according to IEC60947-3(ed.3.2):2015,UL508i.Utilization category DC-PV1. |
Pole number |
Circuit |
Model |
600V |
800V |
1000V |
1200V |
1500V |
32 |
26 |
13 |
10 |
5 |
16 |
8 |
YCRS-13 16 |
40 |
30 |
20 |
12 |
6 |
16 |
8 |
YCRS-20 16 |
55 |
40 |
25 |
15 |
8 |
16 |
8 |
YCRS-25 16 |
/ |
50 |
40 |
30 |
20 |
16 |
8 |
YCRS-40 16 |
/ |
55 |
50 |
40 |
30 |
16 |
8 |
YCRS-50 16 |
32 |
26 |
13 |
10 |
5 |
18 |
8 |
YCRS-13 18 |
40 |
30 |
20 |
12 |
6 |
18 |
8 |
YCRS-20 18 |
55 |
40 |
25 |
15 |
8 |
18 |
8 |
YCRS-25 18 |
/ |
50 |
40 |
30 |
20 |
18 |
8 |
YCRS-40 18 |
/ |
55 |
50 |
40 |
30 |
18 |
8 |
YCRS-50 18 |
32 |
26 |
13 |
10 |
5 |
20 |
10 |
YCRS-13 20 |
40 |
30 |
20 |
12 |
6 |
20 |
10 |
YCRS-20 20 |
55 |
40 |
25 |
15 |
8 |
20 |
10 |
YCRS-25 20 |
/ |
50 |
40 |
30 |
20 |
20 |
10 |
YCRS-40 20 |
/ |
55 |
50 |
40 |
30 |
20 |
10 |
YCRS-50 20 |
Note: RP Rapid Shutdown Switch/Panel
Sketch map
YCRS-2/4P/4B series
YCRS-2/4P/4B series
YCRS-10 series
YCRS-12~20 series
Wiring Diagram
Overall and mounting dimensions(mm)
2P/4P
6P
8P
10P
12~20P
Note: the fire safety switch cannot be installed in the place with direct sunlight, and the sun visor is recommended.
The specific specifications are subject to the specific product packaging.