YCM8-PV Photovoltaic DC MCCB

Features

● Ultra-wide breaking capacity: rated working voltage up to DC1500V and rated current up to 800A. Under DC1500V working conditions, Icu =Ics=20KA, ensuring reliable short-circuit protection. ● Small size: for frame currents up to 320A, the 2P rated working voltage can reach DC1000V, and for frame currents of 400A and above, the 2P rated working voltage can reach DC1500V. ● Ultra-long arc-extinguishing chamber: the arc-extinguishing chamber has been improved as a whole, with more arc- extinguishing plates, greatly improving the product's breaking characteristics. ● Application of narrow-slot arc-extinguishing technology: advanced current-limiting and narrow-slot arc-extinguishing technology is applied, which enables the high voltage and high short-circuit current to be cut off very quickly, facilitating the extinguishing of the arc in the shortest possible time, effectively limiting the energy and current peak, and greatly reducing damage to cables and equipment caused by short-circuit currents.

Selection

YCM8 250 S PV / 3 125A DC1500
Model Shell frame current Breaking capacity Product type Number of poles Rated  current Rated  voltage
YCM8 125(50~125)   250(63~250)   320(250~320) 400(225~400) 630(400~630) 800(630~800) S: Standard breaking N: Higher breaking PV: Photovoltaic/ direct-current 2 3 50, 63, 80, 100, 125, 140, 160, 180, 200, 225, 250, 280, 315, 320, 350, 400, 500, 630, 700, 800 DC500 DC1000 DC1500
Note: The tripping type of this product is thermal-magnetic type The working voltage of YCM8-250/320PV 2P is DC1000V; The working voltage of 3P is DC1500V; YCM8-400/630/800PV 2P and 3P can work under DC1500.

Accessory selection

YCM8 MX 1 AC230V
Model Accessories Adapter   shell frame Accessory voltage
YCM8 OF: Auxiliary contact MX: Shunt release SD: Alarm module Z: Manual operation mechanism P: Electric operating mechanism TS2: Terminal shield 2P TS3: Terminal shield 3P 0:125 1:250/320/ 2:400/630/800 MX: AC110V AC230V AC400V DC24V DC110V DC220V P: AC400V AC230V DC220V

Technical data

Model YCM8- 125PV YCM8- 250PV YCM8- 320PV
Appearance
Shell frame current Inm(A) 125 250 320
Number of poles of products 2 2 3 2 3
DC working voltage(V) 250 500 500 1000 1500 500 1000 1500
Rated insulation voltageUi(V) DC1000 DC1250 DC1500 DC1250 DC1500
Rated impulse withstand voltage Uimp(KV) 8 8 12 8 12
Rated current In(A) 50, 63, 80, 100, 125 63, 80, 100, 125,140, 160, 180, 200, 225, 250 280, 315, 320
Ultimate short-circuit breaking capacity Icu (kA) S 40 40(5ms) 50 20 20 50 20 20
N / / /
Running short-circuit breaking capacity Ics(kA) Ics=100%Icu
Wiring method Up in and down out, down in and up out,    Down in and up out, up in and down out(3P)
Isolation function Yes
Tripping type Thermal-magnetic type
Electrical life(time) 5000 3000 3000 2000 1500 3000 2000 1500
Mechanical life(time) 20000 20000 20000
Standard IEC/EN60947-2
Attached accessories Shunt、Alarm、Auxiliary、Manual operation、Electric operation
Certifications CE
Overalldimension (mm)   Width(W) 64 76 107 76 107
Height(H) 150 180 180
Depth(D) 95 126 126
Note: ① 2P connection in series, ② 3P connection in series

Technical data

Model YCM8- 400PV YCM8-630PV YCM8- 800PV
Appearance    
Shell frame current Inm(A) 400 630 800
Number of poles of products 2 3 2 3 2 3
DC working voltage(V) 500 1000 1500 1500 500 1000 1500 1500 500 1000 1500 1500
Rated insulation voltageUi(V) DC1500 DC1500 DC1500
Rated impulse withstand voltage Uimp(KV) 12 12 12
Rated current In(A) 225, 250, 315,350, 400 400,500,630 630,700,800
Ultimate short-circuit breaking capacity Icu (kA) S 65 35 15 15① 20② 35 15① 20② 65 35 15 15① 20②
N 70 40 20 20① 25② 20① 25② 70 40 20 20① 25②

Running short-circuit breaking capacity Ics(kA)

Ics=100%Icu
Wiring method Up in and down out, down in and up out,    Down in and up out, up in and down out(3P)
Isolation function Yes
Tripping type Thermal-magnetic type
Electrical life(time) 1000 1000 700 500 1000 1000 700 500
Mechanical life(time) 10000 10000
Standard IEC/EN60947-2
Attached accessories Shunt、Alarm、Auxiliary、Manual operation、Electric operation
Certifications CE
Overalldimension (mm) Width(W) 124 182 124 182 124 182
Height(H) 250 250 250
Depth(D) 165 165
Note: ① 2P connection in series, ② 3P connection in series

Accessories

Accessory code Accessory name 125PV 250/320PV 400/630/800PV
SD Alarm contact      
MX Shunt release      
OF Auxiliary contact(1NO1NC)      
OF+OF Auxiliary contact(2NO2NC)  -  -  
MX+OF Shunt release+ Auxiliary contact(1NO1NC)      
OF+OF 2 sets of auxiliary contacts(2NO2NC)      -
MX+SD Shunt release + Alarm contact  -  -  
OF+SD Auxiliary contact + Alarm contact      
MX+OF+SD Shunt release Auxiliary contact(1NO1NC)+ Alarm contact  -  -  
OF+OF+SD 2 sets of auxiliary contacts(2NO2NC)+Alarm contact      

Auxiliary contact

Auxiliary contact current parameters
Rated current of shell frame grade Agreed heating current Ith The rated working current at AC 400V
Inm<320 3A 0.30A
Inm>400 6A 0.40A
Auxiliary contact and its combination
When the circuit breaker is in the "off" position
When the circuit breaker is in the "on" position

Alarm contact

Alarm contact and its combination
Alarm contact Ue=220V, Ith=3A
When the circuit breaker is   in the "off"and "on"position
When the circuit breaker is in the "free trip" position

Shunt release

Generally installed in the Phase A of the circuit breaker, when the rated control power voltage is between 70% - 110%, the shunt releaseshall make the circuit breaker trip reliably under all operating conditions. Control voltage: conventional: AC 50Hz, 110V, 230V, 400V, DC 24V, 110V, 220V. Note: when the power supply of the control circuit is DC24V, the following figure is recommended for the design of the shunt control circuit. KA: DC24V intermediate relay, contact current capacity is 1A K: the microswitch in series with the coil inside the release aid is a normally closed contact. When the circuit breaker is disconnected, the contact will automatically disconnect and close when it is closed.

Wiring diagram

Installation method and overall dimension of external accessories

Model and specification of rotating operating handle mechanism
Model Installation dimension(mm) Central value of the operating handle relative to the circuit breaker(mm)
A B H D
YCM8-250/320PV 157 35 55 50-150 0
YCM8-400/630/800PV 224 48 78 50-150 ±5
Schematic diagram of hole opening of rotating operating handle

Overall and mounting dimension of external accessories

Model and specification of rotating operating handle mechanism
Model H B B1 A A1 D
YCM8-250/320PV 188.5 116 126 90 35 4.2
YCM8-400/630/800PV 244 176 194 130 48 6.5
Outline and installation dimension diagram of CD2

Wiring diagram

Wiring diagram

Overall and mounting dimensions(mm)

YCM8-125PV YCM8-250PV、320PV YCM8-400PV、630PV、800PV Installation drawing of YCM8-PV with arcing cover
Circuit breaker Arcing cover length A Total length B
YCM8-250/320PV 64 245
YCM8-400/630/800PV 64 314

Safety distance when installing circuit breaker

Model L A B C E
Without zero arcing cover With zero   arcing cover Without zero arcing cover With zero   arcing cover
YCM8-250PV 40 50 65 25 25 50 130
YCM8-320PV 40 50 65 25 25 50 130
YCM8-400PV 70 100 65 25 25 100 130
YCM8-630PV 70 100 65 25 25 100 130
YCM8-800PV 70 100 65 25 25 100 130

Temperature correction factor table

Product shell frame Working current In
40℃ 45℃ 50℃ 55℃ 60℃ 65℃ 70℃
250 1 1 1 0.97 0.95 0.93 0.9
320 1 0.96 0.94 0.92 0.9 0.88 0.85
400 1 1 1 0.97 0.95 0.93 0.9
630 1 1 0.98 0.95 0.92 0.89 0.87
800 1 0.94 0.92 0.9 0.87 0.84 0.8
Note: 1. When the ambient temperature is lower than 50 ℃, the product can be used normally without derating; 2. The above derating factors are measured at the rated current of the shell frame.

Use of derating table at high altitude

Product shell frame 250 320 400 630 800
Rated work Current A Rated working  voltage V Rated power frequency   withstand   voltage V Rated work Current A Rated working  voltage V Rated power frequency   withstand   voltage V Rated work Current A Rated working  voltage V Rated power frequency   withstand   voltage V Rated work Current A Rated working  voltage V Rated power frequency   withstand   voltage V Rated work Current A Rated working  voltage V Rated power frequency   withstand   voltage V
2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
2.5 1 1 1 0.94 1 1 1 1 1 1 1 1 0.94 1 1
3 1 0.98 0.98 0.92 0.98 0.98 1 0.98 0.98 0.98 0.98 0.98 0.92 0.98 0.98
3.5 1 0.95 0.95 0.9 0.95 0.95 1 0.95 0.95 0.95 0.95 0.95 0.9 0.95 0.95
4 1 0.92 0.92 0.87 0.92 0.92 1 0.92 0.92 0.92 0.92 0.92 0.87 0.92 0.92
4.5 0.98 0.89 0.89 0.84 0.89 0.89 0.98 0.89 0.89 0.89 0.89 0.89 0.84 0.89 0.89
5 0.96 0.86 0.86 0.82 0.86 0.86 0.97 0.86 0.86 0.86 0.86 0.86 0.8 0.86 0.86

Curve