Features
● Modular design, small size;
● Standard Din rail installation, convenient installation;
● Overload, short circuit, isolation protection function, comprehensive protection;
● Current up to 63A, 14 options;
● The breaking capacity reaches 6KA, with strong protection capacity;
● Complete accessories and strong expansibility;
● Multiple wiring methods to meet various wiring needs of customers;
● The electrical life reaches 10000 times, which is suitable for the 25-year life cycle of photovoltaic.
Selection
YCB8 |
- |
63 |
PV |
4P |
C |
20 |
DC250 |
+ |
YCB8-63 OF |
Model |
Shell grade current |
Usage |
Number of poles |
Tripping |
Rated current |
Rated voltage |
Accessories |
characteristics |
YCB8-63 OF: Auxiliary |
Miniature
circuit
breaker |
63 |
PV: heteropolarity
Pvn: nonpolarity |
1P |
B C K |
1A, 2A, 3A....63A |
DC250V |
YCB8-63 SD: Alarm |
2P |
DC500V |
YCB8-63 MX: Shunt release |
3P |
DC750V |
|
4P |
DC1000V |
|
Note: The rated voltage is affected by the number of poles and wiring mode.
The single poleis DC250V, the two poles in series are DC500V, and so on.
Technical data
Standards |
IEC/EN 60947-2 |
Number of poles |
1P |
2P |
3P |
4P |
Rated current of shell frame grade |
63 |
Electrical performance |
Rated working voltage Ue(V DC) |
250 |
500 |
750 |
1000 |
Rated current In(A) |
1、2、3、4、6、10、16、20、25、32、40、50、63 |
Rated insulation voltage Ui(V DC) |
1200 |
Rated impulse voltage Uimp(KV) |
4 |
Ultimate breaking capacity Icu(KA)(T=4ms) |
Pv:6 PVn: |
Operation breaking capacity Ics(KA) |
Ics=100%Icu |
Curve type |
Type B, Type C, Type K |
Tripping type |
Thermomagnetic |
Service life (time) |
Mechanical |
20000 |
Electrical |
PV:1500 PVn:300 |
Polarity |
Heteropolarity |
Inline methods |
Can be up and down into the line |
Electrical accessories |
Auxiliary contact |
□ |
Alarm contact |
□ |
Shunt release |
□ |
Applicable environmental conditions and installation |
Working temperature(℃) |
-35~+70 |
Storage temperature(℃) |
-40~+85 |
Moisture resistance |
Category 2 |
Altitude(m) |
Use with derating above 2000m |
Pollution degree |
Level 3 |
Protection degree |
IP20 |
Installation environment |
Places without significant vibration and impact |
Installation category |
Category II 、Category III |
Installation method |
DIN35 standard rail |
Wiring capacity |
2.5-25mm² |
Terminal torque |
3.5N·m |
■ Standard □ Optional ─ No
Grounding and fault effect
Grounding type |
Single-stage grounding system |
Ungrounded system |
Circuit diagram |
|
|
Fault effect |
Fault A |
Maximum short-circuit current ISC |
Fault A |
No effect |
Fault B |
Maximum short-circuit current ISC |
Fault B |
Maximum short-circuit current ISC |
Fault C |
No effect |
Fault C |
No effect |
Wiring diagram
Overall and mounting dimensions(mm)
Curve
Temperature correction factor table
Current correction value used in different environments
Environmental
temperature
(℃) |
-35 |
-30 |
-20 |
-10 |
0 |
10 |
20 |
30 |
40 |
50 |
60 |
70 |
Current
correction value
(A) |
Rated current(A) |
1 |
1.3 |
1.26 |
1.23 |
1.19 |
1.15 |
1.11 |
1.05 |
1 |
0.96 |
0.93 |
0.88 |
0.83 |
2 |
2.6 |
2.52 |
2.46 |
2.38 |
2.28 |
2.2 |
2.08 |
2 |
1.92 |
1.86 |
1.76 |
1.66 |
3 |
3.9 |
3.78 |
3.69 |
3.57 |
3.42 |
3.3 |
3.12 |
3 |
2.88 |
2.79 |
2.64 |
2.49 |
4 |
5.2 |
5.04 |
4.92 |
4.76 |
4.56 |
4.4 |
4.16 |
4 |
3.84 |
3.76 |
3.52 |
3.32 |
6 |
7.8 |
7.56 |
7.38 |
7.14 |
6.84 |
6.6 |
6.24 |
6 |
5.76 |
5.64 |
5.28 |
4.98 |
10 |
13.2 |
12.7 |
12.5 |
12 |
11.5 |
11.1 |
10.6 |
10 |
9.6 |
9.3 |
8.9 |
8.4 |
13 |
17.16 |
16.51 |
16.25 |
15.6 |
14.95 |
14.43 |
13.78 |
13 |
12.48 |
12.09 |
11.57 |
10.92 |
16 |
21.12 |
20.48 |
20 |
19.2 |
18.4 |
17.76 |
16.96 |
16 |
15.36 |
14.88 |
14.24 |
13.44 |
20 |
26.4 |
25.6 |
25 |
24 |
23 |
22.2 |
21.2 |
20 |
19.2 |
18.6 |
17.8 |
16.8 |
25 |
33 |
32 |
31.25 |
30 |
28.75 |
27.75 |
26.5 |
25 |
24 |
23.25 |
22.25 |
21 |
32 |
42.56 |
41.28 |
40 |
38.72 |
37.12 |
35.52 |
33.93 |
32 |
30.72 |
29.76 |
28.16 |
26.88 |
40 |
53.2 |
51.2 |
50 |
48 |
46.4 |
44.8 |
42.4 |
40 |
38.4 |
37.2 |
35.6 |
33.6 |
50 |
67 |
65.5 |
63 |
60.5 |
58 |
56 |
53 |
50 |
48 |
46.5 |
44 |
41.5 |
63 |
83.79 |
81.9 |
80.01 |
76.86 |
73.71 |
70.56 |
66.78 |
63 |
60.48 |
58.9 |
55.44 |
52.29 |
Use of derating table at high altitude
Tripping type |
Rated current(A) |
Current correction factor |
Example |
≤2000m |
2000-3000m |
≥3000m |
B、C、K |
1, 2, 3, 4, 6,
10, 13, 16, 20, 25
32, 40, 50, 63 |
1 |
0.9 |
0.8 |
The rated current of 10A
products is 0.9× 10=9A after derating at 2500m |
Recommended wiring size
Wiring capacity
Rated current In(A) |
Nominal cross-sectional area of copper conductor(mm²) |
1~6 |
1 |
10 |
1.5 |
13、16、20 |
2.5 |
25 |
4 |
32 |
6 |
40、50 |
10 |
63 |
16 |
Power consumption per pole of circuit breaker
Rated current In(A) |
Maximum power consumption per stage(W) |
1~10 |
2 |
13~32 |
3.5 |
40~63 |
5 |
Accessories
The following accessories are suitable for YCB8-63PV series, which can provide the functions of remote control of circuit breaker, automatic disconnection of fault circuit, status indication (breaking/closing/fault tripping).
a. The total width of the accessories assembled is within 54mm, the order and quantity from left to right: OF, SD(3max) + MX, MX+OF+MCB, SD can only assemble up to 2 pieces ;
b. Assembled with the body, no tools required;
c. Before installation, check whether the technical parameters of the product meet the requirements of use, and operate the handle to open and close several times to check whether the mechanism is reliable.
Miniature circuit breaker accessories
● Auxiliary contact OF
Remote indication of closing/opening status of circuit breaker.
● Alarm contact SD
When the circuit breaker fault trips, it sends out a signal, together with a red indicator on the front of the device.
● Shunt release MX
When the power supply voltage is 70%~110%Ue, the remote control circuit breaker trips after receiving the signal.
● Minimum making and breaking current: 5mA(DC24V)
● Service life: 6000 times (operating frequency: 1s)
Technical data
Model |
YCB8-63 OF |
YCB8-63 SD |
YCB8-63 MX |
Appearance |
|
|
|
Types |
|
|
|
Number of contacts |
1NO+1NC |
1NO+1NC |
/ |
Control voltage (V AC) |
|
|
110-415
48
12-24 |
Control voltage(V DC) |
|
|
110-415
48
12-24 |
Working current of contact |
AC-12
Ue/Ie: AC415/3A
DC-12
Ue/Ie: DC125/2A |
/ |
Shunt control voltage |
|
Ue/Ie:
AC:220-415/ 0.5A
AC/DC:24-48/3 |
Width(mm) |
9 |
9 |
18 |
Applicable Environmental Conditions and Installation |
Storage temperature(℃) |
-40℃~+70℃ |
Storage humidity |
the relative humidity does not exceed 95% when at +25℃ |
Protection degree |
Level 2 |
Protection degree |
IP20 |
Installation environment |
Places without significant vibration and impact |
Installation category |
Category II 、Category III |
Installation method |
TH35-7.5/DIN35 rail installation |
Maximum wiring capacity |
2.5mm² |
Terminal torque |
1N·m |
Overall and mounting dimensions(mm)
OF/SD Outline and installation dimensions
MX+OF Outline and installation dimensions