YCB8-125PV Photovoltaic DC MCB

Features

● Modular design, small size; ● Standard Din rail installation, convenient installation; ● Overload, short circuit, isolation protection function, comprehensive protection; ● Current up to 125A, 4 options; ● The breaking capacity reaches 6KA, with strong protection capacity; ● Complete accessories and strong expansibility; ● Multiple wiring methods to meet various wiring needs of customers; ● The electrical life reaches 10000 times, which is suitable for the 25-year life cycle of photovoltaic.

Selection

YCB8 125 PV 4P 63 DC250 + YCB8-63 OF
Model Shell grade current Usage Number of poles Rated  current Rated  voltage Accessories
Miniature circuit breaker 125 Photovoltaic/ direct-current PV: heteropolarity Pvn: nonpolarity 1P 63A, 80A, 100A, 125A DC250V YCB8-125 OF: Auxiliary
2P DC500V YCB8-125 SD: Alarm
3P DC750V YCB8-125 MX: Shunt
4P DC1000V
Note: The rated voltage is affected by the number of poles and wiring mode. The single poleis DC250V, the two poles in series are DC500V, and so on.

Technical data

Standard IEC/EN 60947-2
Number of poles 1P 2P 3P 4P
Rated current of shell frame grade 125
Electrical performance
Rated working voltage Ue(V DC) 250 500 750 1000
Rated current In(A) 63、80、100、125
Rated insulation voltage Ui(V DC) 500VDC per pole
Rated impulse voltage Uimp(KV) 6
Ultimate breaking capacity Icu(kA) Pv:6 PVn:10
Operation breaking capacity Ics(KA) PV:Ics=100%Icu  PVn:Ics=75%Icu
Curve type li=10ln(default)
Tripping type Thermomagnetic
Service life (time) Mechanical 20000
Electrical PV:1000  PVn:300
Polarity Heteropolarity
Inline methods Can be up and down into the line
Electrical accessories
Auxiliary contact
Alarm contact
Shunt release
Applicable environmental conditions and installation
Working temperature(℃) -35~+70
Storage temperature(℃) -40~+85
Moisture resistance Category 2
Altitude(m) Use with derating above 2000m
Pollution degree Level 3
Protection degree IP20
Installation environment Places without significant vibration and impact
Installation category Category III
Installation method DIN35 standard rail
Wiring capacity 2.5-50mm²
Terminal torque 3.5N·m
■ Standard   □ Optional   ─ No

Wiring diagram

Overall and mounting dimensions(mm)

Tripping characteristics

Circuit breaker under normal installation conditions and reference ambient temperature (30~35)℃
Tripping type DC current Initial state Appointed time Expected results
All types 1.05In Cold state t≤2h No tripping
1.3In Thermal state t<2h Tripping
Ii=10In 8In Cold state t≤0.2s No tripping
12In t<0.2s Tripping

Curve

Temperature correction factor table

Current correction value for different ambient temperatures
                       Temperature (℃) Rated current (A) -25 -20 -10 0 10 20 30 40 50 60
63A 77.4 76.2 73.8 71.2 68.6 65.8 63 60 56.8 53.4
80A 97 95.5 92.7 89.7 86.6 83.3 80 76.5 72.8 68.9
100A 124.4 120.7 116.8 112.8 108.8 104.5 100 95.3 90.4 87.8
125A 157 152.2 147.2 141.9 136.5 130.8 125 118.8 112.3 105.4

Use of derating table at high altitude

Current correction factor at different altitudes
Rated current(A) Current correction factor
≤2000m 2000-3000m ≥3000m
63, 80, 100, 125 1 0.9 0.8
Example: If a circuit breaker with a rated current of 100A is used at an altitude of 2500m, the rated current must bederated to 100A×90%=90A

Power consumption per pole of circuit breaker and wiring size

Rated current In(A) Nominal cross-section of copper conductor(mm²) Maximum power consumption per pole(W)
63 16 13
80 25 15
100 35 15
125 50 20

Accessories

The following accessories are compatible with the YCB8-125PV series circuit breakers. They enable functions such as remote operation, automatic fault circuit disconnection, and status indication (open/closed/fault trip).

Key Features

a. The total combined width of the accessories is no more than 54mm. They can be arranged in the following sequence (from left to right): OF, SD (up to 3 pieces max) + MX, MX + OF, MV + MN, MV (up to 1 piece max) + MCB. Note that a maximum of 2 SD units can be assembled. b. Accessories are easily assembled onto the main body without requiring tools. c. Before installation, verify that the product’s specifications meet usage requirements. Test the mechanism by operating the handle to open and close a few times, ensuring reliable performance.

Accessory Functions

● Auxiliary Contact (OF): Provides remote signaling of the circuit breaker’s open/closed status. ● Alarm Contact (SD): Sends a signal when the circuit breaker trips due to a fault, accompanied by a red indicator on the device’s front panel. ● Shunt Release (MX): Enables remote tripping of the circuit breaker when the supply voltage is within 70%-110% of Ue. ● Minimum operational current: 5mA (DC24V). ● Service life: 6,000 operations (1-second intervals).

Technical data

Model YCB8-125 OF YCB8-125 SD YCB8-125 MX
Appearance      
Types      
Number of contacts 1NO+1NC 1NO+1NC /
Control voltage (V AC) 110-415 48 12-24
Control voltage(V DC) 110-415 48 12-24
Working current of contact AC-12 Ue/Ie: AC415/3A DC-12 Ue/Ie: DC125/2A /
Shunt control voltage Ue/Ie: AC:220-415/ 0.5A AC/DC:24-48/3
Width(mm) 9 9 18
Applicable Environmental Conditions and Installation
Storage temperature(℃) -40℃~+70℃
Storage humidity the relative humidity does not exceed 95% when at +25℃
Protection degree Level 2
Protection degree IP20
Installation environment Places without significant vibration and impact
Installation category Category II 、Category III
Installation method TH35-7.5/DIN35 rail installation
Maximum wiring capacity 2.5mm²
Terminal torque 1N·m

Overall and mounting dimensions(mm)

Alarm Contact Outline and installation dimensions MX+OF Outline and installation dimensions MX Outline and installation dimensions